Timer mode
POUT1 TIMER1: output active:low
ON: 10:50:00 OFF: 11:00:00
POUT1 TIMER2: output active:low
ON: 13:00:00 OFF: 14:00:00
POUT1 TIMER1: output active:low
ON: 23:45:00 OFF: 09:30:00
If Timer mode is selected, a window as shown above is displayed. The switching plan
is assigned per day. Three turn-on and turn-off times are programmable for each
output. If a switching time has to be configured, only the turn-on and turn-off time
must be programmed. Thus the example shows switching times from 10:50 to 11:00,
13:00 to 14:00 and 23:45 to 09:30. A turn-off time earlier than the turn-off time
would cause the output to be enabled over midnight. For example a program 'ON
Time' 10:45:00, 'OFF Time' 9:30:00 would cause an active ouput from 10:45 to 9:30
(the next day!). If one or more of the three switching times are unused just enter the
same time into the fields 'ON Time' and 'OFF Time'. In this case the switch time
does not affect the output.
Single Pulse
Selecting Single Pulse generates a single pulse of defined length once per day.
POUT1 SINGLE: output active:low
TIME: 12:00:00 LNG: 00.10 sec
You can enter the time when the pulse is generated in the field 'Time'. The value in
field 'LNG' determines the pulse duration. A pulse duration from 10 msec to 10 sec
in steps of 10 msec can be selected.
The example shows a single pulse at 12:00 every day with a duration of 100 ms.
35